MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 221
English
Network parameters for the PL calculation
Architecture:
Cat.2
Diagnostic coverage:
DC = 90%
Reliability of Module M1:
MTTFd = 437 (years)
Logical block diagram of a safety function using the network
INPUT
M1 n°1
M1 n°2
M1 n°3
M1 n°4
OUTPUT
LOGIC (NETWORK)
Example of application in Category 4 according to ISO 13849-1:
Network data flow
Figure 87
Network parameters for the PL calculation
Architecture:
Cat.4
Diagnostic coverage:
DC = 99%
PFH Module M1:
PFHd = 6,86E-09 (hour
-1
)

Table of Contents