MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 81
English
MOR4 (Figure 43)
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL 0/1
RELAY 1/4
CLEAR1/4
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
Internal fault
OFF
2 / 3 flashes
OFF
Shows the
physical address
of the unit
Rosso
OFF
Return the unit to ReeR
to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
Relais output error
OFF
4
flashes
OFF
4 flashes
(only the LED
corresponding to the
output in FAIL mode)
OFF
If the problem persists,
return the module to
ReeR to be repaired
Error in
communication with
master
OFF
5
flashes
OFF
OFF
OFF
Restart the system
If the problem persists,
return the module to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
OFF
Restart the system
Check which unit is in
FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
Change the unit's
address (see NODE SEL)
External contactors
feedback error on
Category 4 relay
ON
OFF
4
flashes
4 flashes
(only the LEDs corresponding to the
outputs in FAIL mode)
Verify connections
5,6,7,8.
Error on node
detection circuit
OFF
3 flashes
OFF
3
flashes
OFF
OFF
Return the module to
ReeR to be repaired
Table 73 - Troubleshooting MOR4
Figure 43 -
MOR4

Table of Contents

Other manuals for Reer MOSAIC MI8O4C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer MOSAIC MI8O4C and is the answer not in the manual?

Reer MOSAIC MI8O4C Specifications

General IconGeneral
BrandReer
ModelMOSAIC MI8O4C
CategoryController
LanguageEnglish

Related product manuals