MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 37
English
RESTART_FBK
The RESTART_FBK signal input allows the MOSAIC to verify an EDM (External Device
Monitoring) feedback signal (series of contacts) from the external contactors, and to
monitor Manual/Automatic operation (See the list of possible connections in Table 24).
 If the application requires it, the response time of the external contactors must be verified by
an additional device.
 The RESTART command must be installed outside the danger area in a position where the
danger area and the entire work area concerned are clearly visible.
 It must not be possible to reach the control from inside the danger area.
MODE OF
OPERATION
EDM
RESTART_FBK
AUTOMATIC
With K1_K2
control
K2
K1
24V
ext_Restart_fbk
Without
K1_K2
control
24V
ext_Restart_fbk
MANUAL
With K1_K2
control
K2
K1
24V
ext_Restart_fbk
Without
K1_K2
control
24V
ext_Restart_fbk
Table 24

Table of Contents

Other manuals for Reer MOSAIC MI8O4C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer MOSAIC MI8O4C and is the answer not in the manual?

Reer MOSAIC MI8O4C Specifications

General IconGeneral
BrandReer
ModelMOSAIC MI8O4C
CategoryController
LanguageEnglish

Related product manuals