MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 83
English
MOS8 (Figure 45)
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL0/1
STATUS1/8
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
2 / 3 flashes
OFF
Shows the physical
address of the unit
OFF
Return the unit to ReeR
to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
Error in communication
with master
OFF
5
flashes
OFF
OFF
Restart the system
If the problem persists,
return the module to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
Restart the system
Check which unit is in
FAIL mode
Same type of slave with
same address detected
OFF
5
flashes
5
flashes
OFF
Change the unit's
address
(see NODE SEL)
Error on node detection
circuit
OFF
3 flashes
OFF
3
flashes
OFF
Return the module to
ReeR to be repaired
Short circuit or overload
detected on status 1-8
output
OFF
OFF
ON
OFF
flash
Verify output status 1-
8 connections
Power supply missing
on status 1-8 output
OFF
OFF
ON
OFF
flash
alternatively
Connect 5 pin to power
supply
Table 75 - Troubleshooting MOS8
Figure 45 MOS8

Table of Contents

Other manuals for Reer MOSAIC MI8O4C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer MOSAIC MI8O4C and is the answer not in the manual?

Reer MOSAIC MI8O4C Specifications

General IconGeneral
BrandReer
ModelMOSAIC MI8O4C
CategoryController
LanguageEnglish

Related product manuals