MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 125
English
TWO-HAND (bimanual control)
The TWO HAND function block verifies the status of the
inputs of a two hand control switch. Only if both the
press-buttons are pressed within 500 ms the output is 1
(TRUE). Otherwise the output is 0 (FALSE).
Input type:
- Double NO Allows connection of two-hand switch
with one NO contact for each button (EN 574 III A).
- Quadruple NC-NO - Allows connection of two-hand
switch with a double NO/NC contact for each button
(EN 574 III C).
Quadruple NC/NO correct connection
Contacts NO to terminal corresponding to IN1, IN3
Contacts NC to terminal corresponding to IN2, IN4
Parameters
Output test: This is used to select which test output signals are to be sent to the component
contacts. This additional control permits detection and management of any short-circuits
between the lines. To enable this control, the test output signals must be configured
(amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by pressing the two buttons (within 500 ms) and releasing them to
run a complete function test and enable the output. This test is only requested at machine
start-up (when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the mode selector. The filter can
be configured to between 3 and 250 ms and eliminates any bouncing on the contacts. The
length of the filter affects the calculation of the unit's total response time.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
NETWORK_IN
This functional block implements a Network
connection input interface; it generates an LL1 in
the OUT output when the line is high, otherwise
an LL0.
Parameters
Type of input:
- Single - enables the connection of Signalling
outputs of an external M1/M1S unit.
- Double - enables the connection of OSSD outputs of an external M1/M1S unit.
Filter (ms): Enables the filtering of signals from an external M1/M1S unit.
This filter can be set to between 3 and 250ms. The length of the filter affects the calculation
of the unit's total response time.
This input can only be allocated on M1
This input must be used when Mosaic OSSD outputs are connected to the inputs of a
second downstream Mosaic or together with the NETWORK operator.

Table of Contents

Other manuals for Reer MOSAIC MI8O4C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer MOSAIC MI8O4C and is the answer not in the manual?

Reer MOSAIC MI8O4C Specifications

General IconGeneral
BrandReer
ModelMOSAIC MI8O4C
CategoryController
LanguageEnglish

Related product manuals