LED INDICATORS (Troubleshooting)
Master M1 (Figure 34)
Table 64 - Troubleshooting M1
Figure 34 - M1
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
COM
IN1÷8
ENA
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
BLUE
RED/GREEN
YELLOW
YELLOW
Internal fat
OFF
2 or 3
flashes
OFF
OFF
OFF
OFF
Red
OFF
OFF
Return the unit to
ReeR to be repaired
OSSD output
error
OFF
4
flashes
OFF
OFF
OFF
OFF
4 flashes
(only the LED
corresponding to
the output in FAIL
mode)
OFF
OFF
• Check the
OSSD1/2
connections
• If the problem
persists return the
M1 to ReeR to be
repaired
Error in
communication
with slave
OFF
5
flashes
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• Restart the
system.
• If the problem
persists return the
M1 to ReeR to be
repaired
Slave unit
error
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• Restart the system
• Check which unit
is in FAIL mode
MCM error
OFF
6
flashes
OFF
6
flashes
OFF
OFF
OFF
OFF
OFF
Replace the MCM

Table of Contents

Other manuals for Reer MOSAIC MI8O4C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer MOSAIC MI8O4C and is the answer not in the manual?

Reer MOSAIC MI8O4C Specifications

General IconGeneral
BrandReer
ModelMOSAIC MI8O4C
CategoryController
LanguageEnglish

Related product manuals