MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
210 8540780 • 10/07/2020 • Rev.38
Manual Reset:
ï‚· Should the INPUT be active (TRUE), the reset enables the output of the function block.
ï‚· Should the INPUT be not active (FALSE), the output of the function block follows the
OVERRIDE request.
There are two types of reset: Manual and Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double transition
from 0 to 1 and then back to 0 is verified.
5s > t1 > 250 ms
t2 = 250 ms