4-2 Technical Data IndraControl L40
DOK-CONTRL-IC*L40*****-PR03-EN-P
Note: The power consumption of the IndraControl L40 (without
additional modules and without connected I/O) is typically
9 watts.
4.3 Ambient Conditions
In operation Storage/Transport
Max. surrounding air temperature +5 ... +55 °C
If the load is higher or if the surrounding
air temperature is > 45 °C, the optionally
available blower must be used!
-25 °C to +70 °C
Relative humidity RH-2; 5 % to 95 % according to
DIN EN 61131-2,
non-condensing.
Air pressure Up to 2,700 m above MSL according to
DIN 60204
Up to 3,000 m above MSL according
to DIN 60204
Mechanical strength Max. vibration:
Frequency range: 10...150 Hz
Excursion: 0.075 mm
for 10...0.57 Hz
Acceleration: 1 g
for 57...150 Hz
According to EN 60068-2-6
Max. shock:
15 g according to EN 60 068-2-27, no
disturbance of the function
Degree of pollution 2 2
Fig. 4-3: Ambient conditions
Note: The surrounding air must be free from acids, alkaline
solutions, corrosive agents, salts, metal vapors, and other
electrically conductive contaminants in high concentrations.
The ambient air must be free from dust. Housings and
installation compartments must at least comply with degree of
protection IP 54 according to DIN VDE 0470-1.