26 Rockwell Automation Publication 2713P-UM001G-EN-P - May 2022
Chapter 2
Prepare for Panel
Mounting
Before mounting a terminal in a panel, read this section and the entire installation
procedure on page 29
.
Mounting levers insert into the slots around the bezel to secure the terminal in
the panel. The number of mounting levers varies by terminal size.
Each slot has six notches with alignment marks that are locking positions for a
mounting lever. The thickness of the panel that you mount the terminal in
determines the locking position that is required to maintain a NEMA, UL Type,
and IP seal.
Always orient a mounting lever vertically before inserting it into a slot. This
method is the only way to slide the mounting lever knob within the slot for
positioning. After sliding the mounting lever to a specific notch, rotate the
mounting lever toward the panel to lock it in position. The flat side of the
mounting lever must come into contact with the panel.
IMPORTANT Use catalog number 2711P-RMCP mounting levers (black) for PanelView 5310
terminals. Do not use gray mounting levers; they are not compatible with
PanelView 5310 terminals.
Table 10 - Mounting Lever Locking Positions
Mounting Slot
Mounting
Lever Lock
Position Panel Thickness Range
Typical
Gauge
1
1.50…2.01 mm (0.060…0.079 in.) 16
2
2.03…2.64 mm (0.08…0.104 in.) 14
3
2.67…3.15 mm (0.105…0.124 in.) 12
4
3.17…3.66 mm (0.125…0.144 in.) 10
5
3.68…4.16 mm (0.145…0.164 in.) 8/9
6
4.19…4.80 mm (0.165…0.188 in.) 7