Rockwell Automation Publication 2713P-UM001G-EN-P - May 2022 29
Chapter 2
Mount the Terminal in a
Panel
The PanelView 5310 terminals are designed for single-person installation. No
tools are required except for tools to make the panel cutout.
To mount the terminal in a panel, follow these steps.
1. Use the cutout dimensions on page 24
to cut an opening in the panel.
2. Verify that the sealing gasket is present on the terminal.
This gasket forms a compression seal. Do not use sealing compounds.
3. Insert and stabilize the terminal in the panel cutout.
a. Insert levers in the top corner slots in the orientation that is shown and
rotate the non-flat side of the levers toward panel.
ATTENTION: Disconnect all electrical power from the panel before making the
panel cutout.
Make sure that the area around the panel cutout is clear and that the panel is clean
of any debris, oil, or other chemicals.
Make sure that metal cuttings do not enter any components that are already
installed in the panel and that the edges of the cutout have no burrs or sharp
edges.
Failure to follow these precautions can result in personal injury or damage to panel
components.
TIP The mounting levers for PanelView 5310 terminals are black (catalog
number 2711P-RMCP).
Do not use gray mounting levers; they are not compatible with
PanelView 5310 terminals.
Flat Side