EasyManua.ls Logo

Rockwell Automation SMC Dialog Plus

Rockwell Automation SMC Dialog Plus
189 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Communications
8-19
1203-GD1 Communication Module Switch Settings
The following information is provided to explain the required 1203-
GD1 communication module switch settings for this example. Refer
to the 1203-GD1 manuals for further details related to the switch
settings.
Example Information
This configuration requires a 1/4 rack size allocation.
The SMC Dialog Plus controller does not support Datalinks.
Switch Settings
I/O Addressing
The 1203-GD1 communication module uses 1-slot addressing. Based
on the module switch settings as described above, the discrete I/O can
be mapped to the PLC I/O Image as shown below.
Description Switch Setting
SMC Rack Address: 02
SW1: Switches 1 & 2 (Not Used),
Switches 3-6 & 8 (On), Switch 7 (Off)
Starting Group Address: 0 SW2: Switches 1 & 2 (On)
Last Rack: No SW2: Switch 3 (Off)
Hold Last State: Yes SW2: Switch 4 (On)
Fault on Comm Loss: Yes SW2: Switch 5 (On)
Fault Controller: No SW2: Switch 6 (Off)
R I/O Baud Rate: 115k SW2: Switch 7 (On), Switch 8 (Off)
Block Transfer:
Yes
SW3: Switch 1 (On)
Logic Cmd/Status:
Yes
SW3: Switch 2 (On)
Reference/Feedback:
No
SW3: Switch 3 (Off)
Datalinks:
No
SW3: Switch 4-8 (Off)
SW1
8 7 6 5 4 3 2 1
Not Used
Not Used
On
On
On
On
Off
On
SW2
8 7 6 5 4 3 2 1
Starting Module Group (0)
Starting Module Group (0)
Last Rack Setting (Off)
Hold Last State (On)
Fault on Comm Loss (On)
Fault Controller (Off)
R I/O Baud Rate (115k)
R I/O Baud Rate (115k)
SW3
8 7 6 5 4 3 2 1
Block Transfer On
Logic Cmd/Sts On
Reference/Fdbk Off
Datalink A Off
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
PLC I/O Group Number Output Image Input Image
0 Block Transfer Block Transfer
1 Logic Command Logic Status

Table of Contents

Related product manuals