A-4
Specifications
Assumes the Bulletin 825 converter module is utilized.
The SMC Dialog Plus controller calculates the current values to two decimal place resolution while
displaying only to tenths of Amps. The display accuracy provided is, therefore, reduced by the
truncation. The affect of truncation on accuracy will be dependent on the magnitude of the value.
Assumes a balanced supply.
Other Ratings UL/CSA/NEMA IEC
EMC Emission Levels
Conducted Radio Frequency
Emissions
Class A
Radiated Emissions Class A
EMC Immunity Levels
Electrostatic Discharge 8kV Air Discharge
Radio Frequency Electromagnetic
Field
Per IEC 947-4-2
Fast Transient Per IEC 947-4-2
Surge Transient Per IEC 947-4-2
Overload Characteristics:
Type Solid-state thermal overload with phase loss
Current Range 1.0–999.9 Amps
Trip Classes 10, 15, 20, and 30
Trip Current Rating 120% of Motor FLC
Number of Poles 3
Metering Accuracy
Voltage ± 2%
Current
± 5%
kW ± 10%
kWH ± 10%
Displacement Power Factor
± 3%
Converter Module Output
Cat. No.:
825-MCM20
825-MCM180
825-MCM630
78.8 mV/A
9.85 mV/A
1.231 mV/A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation SMC Dialog Plus and is the answer not in the manual?

Rockwell Automation SMC Dialog Plus Specifications

General IconGeneral
BrandRockwell Automation
ModelSMC Dialog Plus
CategoryController
LanguageEnglish

Related product manuals