Parameter Information
B-3
Table B.1 (cont.) Parameter List
Group
Parameter
Description
Parameter
Number
Display
Units
Scale
Factor
Minimum Maximum
Default
Setting
User
Setting
Basic Setup
(cont.)
Slow Speed with Braking
Slow Speed
Select
44 — — Low, High High
Slow Accel
Current
46 % FLC 1 0 450 0
Slow
Running
Current
47 % FLC 1 0 450 0
Braking
Current
48 % FLC 1 0 400 0
Advanced
Setup
Dual Ramp 29 — — No, Yes No
Ramp Time
#2
32 Seconds 1 0 30 10
Initial Torque
#2
33 % LRT 1 0 90 70
Undervolt
Level
52
% Line
Voltage
1 0 99 0 (Off)
Undervolt
Delay
53 Seconds 1 0 99 0
Overvolt
Level
54
% Line
Voltage
1 0 199 0 (Off)
Overvolt
Delay
55 Seconds 1 0 99 0
Jam Level 56 % FLC 1 0 999 0 (Off)
Jam Delay 57 Seconds 10 0.0 10.0 0
Unbalance
Level
58 % 1 0 25 0 (Off)
Unbalance
Delay
86 Seconds 1 0 99 0
Rebalance 59 — — Off, On Off
Underload
Level
60 % FLC 1 0 99 0 (Off)
Underload
Delay
61 Seconds 1 0 99 0
Phase
Reversal
62 — — Off, On Off
Starts per
Hour
63 — —1 0 99 0 (Off)
Restart
Attempts
64 — 1 0 5 2
Restart Delay 65 Seconds 1 0 60 0
ETM Reset 15 — — Off, On Off
Parameter
Management
17 — —
Ready, Default Init.
Recll Frm EE,Store In EE
Ready