Page #171 background image
B-2
Parameter Information
Table B.1 (cont.) Parameter List
Group
Parameter
Description
Parameter
Number
Display
Units
Scale
Factor
Minimum Maximum
Default
Setting
User
Setting
Basic Setup
(cont.)
Stall Delay 37 Seconds 10 0.0 10.0 0 (Off)
Energy Saver 38 Off, On Off
Aux. Contacts
1 and 2
39 Normal, Up-to-speed Normal
Aux. Contact
3
40 Normal, Fault Normal
Contact 3
Config
41 N.O., N.C. N.O.
Parameter
Mgmt.
17
Ready, Default Init.
Recll Frm EE,Store In EE
Ready
Control Options
Soft Stop
Soft Stop
Time
42 Seconds 1 0 60 0
Pump Control
Starting
Mode
28
Soft Start, Current Limit,
and Pump Start
Soft Start
Pump Stop
Time
42 Seconds 1 0 120
Preset Slow Speed
Slow Speed
Select
44 Low, High High
Slow Speed
Direction
45 Reverse, Forward Forward
Slow Accel
Current
46 % FLC 1 0 450 0
Slow Running
Current
47 % FLC 1 0 450 0
SMB Smart Motor Braking
Braking
Current
48 % FLC 1 0 400 0
Accu-Stop
Slow Speed
Select
44 Low, High High
Slow Accel
Current
46 % FLC 1 0 450 0
Slow Running
Current
47 % FLC 1 0 450 0
Braking
Current
48 % FLC 1 0 400 0
Stopping
Current
51 % FLC 1 0 400 0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation SMC Dialog Plus and is the answer not in the manual?

Rockwell Automation SMC Dialog Plus Specifications

General IconGeneral
BrandRockwell Automation
ModelSMC Dialog Plus
CategoryController
LanguageEnglish

Related product manuals