EasyManua.ls Logo

Rohde & Schwarz SME02 - Transmission Parameters; Interface Functions

Rohde & Schwarz SME02
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SME RS-232-C Interface
1038.6002.02 6A.5 E-12
Transmission parameters
To ensure an error-free and correct data transmission, the parameters of the instrument and the
controller should have the same settings. The parameters are set in menu UTILITIES-SYSTEM-RS232.
Transmission rate The following baud rates can be set in the instrument:
(baud rate) 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200.
Data bits Data transmission is in 8-bit ASCII code. The first bit transmitted
is the LSB (Least Significant Bit).
Start bit Each data byte begins with a start bit. The falling edge of the start
bit indicates the beginning of the data byte.
Parity bit A parity bit is not used.
Stop bit The transmission of a data byte is terminated by a stop bit.
Example:
Transmission of character A (41 hex) in the 8-bit ASCII code.
01 02 03 04 05 06 07 08 09 10
Bit 01 = Start bit Bit 02...09 = Data bits Bit 10 = Stop bit
Bitduration= 1/baud rate
Interface functions
For interface control, some control characters defined from 0 to 20 hex of the ASCII code can be
transmitted via the interface (see Table A-4).
Table A- 4 Interface functions (RS-232-C)
Control character Interface function
<Ctrl Q> 11 hex Enables character output (XON)
<Ctrl S> 13 hex Inhibits character output (XOFF)
Break (at least 1 character only log 0) Reset instrument
0Dhex, 0Ahex Terminator <CR>, <LF>
Switchover between local/remote

Table of Contents

Related product manuals