Product Certifications
93
Product Certifications
March 2017
Reference Manual
00809-0100-4108, Rev CA
Appendix B Product Certifications
Rosemount
™
2088 product certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 93
Rosemount 2090 product certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 98
Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 103
B.1 Rosemount
™
2088
product certifications
Rev 1.11
B.1.1 European Directive
Information
A copy of the EU Declaration of Conformity can be found at
the end of the Quick Start Guide. The most recent revision
of the EU Declaration of Conformity can be found at
Emerson.com/Rosemount
.
B.1.2 Ordinary Location
Certification
As standard, the transmitter has been examined and tested
to determine that the design meets the basic electrical,
mechanical, and fire protection requirements by a
nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health
Administration (OSHA).
B.1.3 North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 1V2A8.AE
Standards: FM Class 3600 – 2011, FM, Class 3615 –
2006,
FM class 3616 – 2011, FM Class 3810 –
2005, ANSI/NEMA 250 – 1991
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1,
GP E, F, G; CL III; T5(–40 °C
≤ T
a
≤ +85 °C);
Factory Sealed; Type 4X
I5 USA Safety (IS) and Nonincendive (NI)
Certificate: 0V9A7.AX
Standards: FM Class 3600 – 1998, FM Class 3610 –
2010,
FM Class 3611 – 2004, FM Class 3810 –
1989
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP
E, F, G; Class III; DIV 1 when connected
per Rosemount drawing 02088-1018; NI
CL 1, DIV 2, GP A, B, C, D; T4(–40 °C
≤ T
a
≤
+70 °C); Type 4x
Special Condition for Safe Use (X):
1. The Rosemount 2088 Transmitter with the transient
terminal block (Option code T1) will not pass the 500
Vrms dielectric strength test and this must be taken
into account during installation.
C6 Canada Explosionproof, Intrinsic Safety and Division 2,
Dust-Ignitionproof
Certificate: 1015441
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CSA
Std C22.2 No. 25-1966, CSA Std C22.2 No.
30-M1986, CAN/CSA-C22.2 No. 94-M91,
CSA Std C22.2 No. 142-M1987,
CAN/CSA-C22.2 No. 157-92, CSA Std
C22.2 No. 213-M1987,
ANSI-ISA-12.27.01-2003
Markings: Explosionproof for Class I, Division 1,
Groups B,C and D; Dust-Ignitionproof Class
II, Division 1, Groups E, F, G; Class III
Division 1; Intrinsically Safe Class I, Division
1 Groups A, B, C, D when connected in
accordance with Rosemount drawing
02088-1024, Temperature Code T3C; Class
I Division 2 Groups A, B, C and D; Type 4X;
Factory Sealed; Single Seal
B.1.4 Europe
ED ATEX Flameproof
Certificate: KEMA97ATEX2378X
Standards: EN60079-0:2012 + A11:2013,
EN60079-1:2014, EN60079-26:2015
Markings: II 1/2 G Ex db IIC T6....T4, Ga/Gb, T6(–60
°C
≤ T
a
≤ +70 °C), T4/T5(–60 °C ≤ T
a
≤ +80
°C)