Product Certifications
March 2017
Reference Manual
00809-0100-4108, Rev CA
Product Certifications
98
Application:
SLL Lloyds Register (LR) Type Approval
Certificate: 11/60002
Application: Environmental categories ENV1, ENV2,
ENV3 and ENV5
B.2 Rosemount 2090
product certification
Rev 1.6
B.2.1 European Directive
Information
A copy of the EU Declaration of Conformity can be found at
the end of the Quick Start Guide. The most recent revision
of the EU Declaration of Conformity can be found at
Emerson.com/Rosemount
.
B.2.2 Ordinary Location
Certification
As standard, the transmitter has been examined and tested
to determine that the design meets the basic electrical,
mechanical, and fire protection requirements by a
nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health
Administration (OSHA).
B.2.3 North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 1V2A8.AE
Standards: FM Class 3600–2011, FM Class 3615–2006,
FM class 3616–2011,
FM Class 3810 - 2005, ANSI/NEMA
250–1991
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP
E, F, G; Class III; when connected per
Rosemount drawing 02088-1018; NI CL 1,
DIV 2, GP A, B, C, D; T4(-40 °C
≤ T
a
≤ +70
°C); Factory Sealed; Type 4x
Special Condition for Safe Use (X):
1. The Model 2088 transmitter with the transient
terminal block (Option code T1) will not pass the
500Vrms dielectric strength test and this must be
taken into account during installation
C6 Canada Explosionproof, Intrinsically Safe, and Division
2, Dust-Ignitionproof
Certificate: 1015441
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CSA
Std C22.2 No. 25-1966, CSA Std C22.2 No.
30-M1986, CAN/CSA-C22.2 No. 94-M91,
CSA Std C22.2 No. 142-M1987,
CAN/CSA-C22.2 No. 157-92, CSA Std
C22.2 No. 213-M1987,
ANSI-ISA-12.27.01-2003
Markings: Explosionproof for Class I, Division 1,
Groups B, C and D; Class II, Groups E, F, and
G; Class III; Intrinsically Safe Class I,
Division 1 when connected in accordance
with Rosemount drawing 02088-1024,
Temperature Code T3C; Ex ia; Class I
Division 2 Groups A, B, C and D; Type 4X;
Factory Sealed
B.2.4 Europe
ED ATEX Flameproof
Certificate: KEMA97ATEX2378X
Standards: EN60079-0:2012 + A11:2013,
EN60079-1:2014, EN60079-26:2015
Markings: II 1/2 G Ex db IIC T6…T4, T6(-60 °C
≤ T
a
≤
+70 °C), T4/T5(-60 °C ≤ T
a
≤ +80 °C);
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm.
Installation, maintenance and use shall take into
account the environmental conditions to which the
diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be
followed in detail to assure safety during its expected
lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from
electrostatic discharge. Avoid installations that
could cause electrostatic build-up on painted
surfaces, and only clean the painted surfaces
with a damp cloth. If paint is ordered through a
special option code, contact the manufacturer
for more information.
I1 ATEX Intrinsic Safety
Certificate: BAS00ATEX1166X
Standards: EN60079-0:2012, EN60079-15:2010
Location classes
Temperature D
Humidity B
Vibration A
EMC B
Enclosure D