Manual – MOVIDRIVE® MDX61B Safety Module MOVISAFE® DCS..B Option
43
5
Measures for electromagnetic compatibility (EMC)
Installation
5.6 Measures for electromagnetic compatibility (EMC)
Option DCS..B is intended for industrial use (based on the EMC test specifications
EN 61800-3). Prerequisite for safe installation is that the electromagnetic compatibility
of the entire system is ensured by taking appropriate measures. The following measures
ensure designated operation of the DCS..B option:
Route voltage supply cables of the DCS..B option and "switching cables" of
MOVIDRIVE
®
MDX61B separately from one another.
Route signal cables and power cables of the inverter in separate cable ducts. The
minimum distance between the cable ducts must be 10 mm.
Use only shielded cables to connect the position and velocity sensors. The cable for
transmitting signals must be suitable for RS485 standard (EIA).
Make sure the shield is connected properly in the 9-pole D-sub connectors of the
position and velocity sensors and on the sensor end of the cable. Use only metal or
metalized connectors.
Use only shielded motor cables.
Ensure EMC-compliant installation of the inverter in the vicinity of the DCS..B option.
Check the routing and design of the shielding for the motor cable and braking resistor
connection.
Connect the shield of the motor cable, encoder cable, and split cable at both sides
(motor and MOVIDRIVE
®
B). The control cables to MOVIDRIVE
®
B must be
shielded. The shield must be connected to MOVIDRIVE
®
B.
Connect the shield of the hybrid motor cable with integrated TF also to the shield
terminal of MOVIDRIVE
®
B.
All contactors near the DCS.. option must be equipped with suitable suppressors.
Use only shielded cables for safety-relevant control cables.
The control cable between X83 of the DCS..B option and X17 of MOVIDRIVE
®
B
must be connected to the shield terminal for signal cables of MOVIDRIVE
®
B.
It is essential that you attach the shielding of the DC 24 V supply cable to the housing
at both ends.