Digital Modules
3-86
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Technical specifications of the SM 322; DO 8 x 120/230 VAC/2 A
Dimensions and Weight
Dimensions W x H x D
(in millimeters)
40 x 125 x 117
Weight Approx. 275 g
Data for Specific Module
Supports clocked
operation
No
Number of outputs 8
Length of cable
Unshielded
Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Rated load voltage L1
Permitted frequency range
120/230 VAC
47 Hz to 63 Hz
Total current of the outputs
(per group)
Horizontal configuration
Up to 40 C max. 4 A
Up to 60 C max. 2 A
Vertical configuration
Up to 40 C max. 2 A
Isolation
Between channels and
backplane bus
Between the channels
In groups of
Yes
Yes
4
Permitted potential difference
Between M
internal
and the
outputs
230 VAC
Between the outputs of the
different groups
500 VAC
Insulation tested with 1500 VAC
Current consumption
From the backplane bus
From load voltage L1
(without load)
max. 100 mA
max. 2 mA
Power dissipation of the module typ. 8.6 W
Status, Interrupts, Diagnostics
Status display Green LED per channel
Interrupts None
Diagnostic functions
Group error display
Yes
Red LED (SF)
2)
Data for Selecting an Actuator
Output voltage
At signal “1”
At maximum current
At minimum current
min. L1 (–1.5 V)
min. L1 (–8.5 V)
Output current
At signal “1”
Rated value AC 2 A
1)
Permitted range for 0 C to
40 C
10 mA to 2 A
Permitted range for 40 C
to 60 C
10 mA to 1 A
Permitted current surge
(per group)
max. 20 A
(not more than 1 AC
scan cycle)
At signal “0”
(leakage current)
max. 2 mA
Output delay (for resistive load)
From “0” to “1” Not more than 1 AC
scan cycle
From “1” to “0” Not more than 1 AC
scan cycle
Minimum load current 10 mA
Zero cross inhibit voltage max. 60 V
Size of the motor starter max. size 5 to NEMA
Lamp load max. 50 W
Connecting two outputs in parallel
For redundant triggering of
a load
Possible (only outputs
of the same group)
To increase performance Not possible
Triggering a digital input Possible
Switch rate
For resistive load
Inductive loads, according
to IEC 947-5-1, AC 15
For lamp load
max. 10 Hz
max. 0.5 Hz
1 Hz
Short-circuit protection
of output
Fuse, 8 A/250 V; per
group
Min. current required for
fuse to blow
min. 40 A
Max. response time max. 300 ms
Replacement fuses
Wickman
Schurter
Littelfuse
8 A fuse/quick-acting
194-1800-0
SP001.1013
217.008
Fuse carrier
Wickman 653 07
1)
The load current must not be half-wave
2)
Potential errors are:
- No load voltage
- Fuse defective

Table of Contents

Other manuals for Siemens 6ES7 305-1BA80-0AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6ES7 305-1BA80-0AA0 and is the answer not in the manual?

Siemens 6ES7 305-1BA80-0AA0 Specifications

General IconGeneral
BrandSiemens
Model6ES7 305-1BA80-0AA0
CategoryController
LanguageEnglish

Related product manuals