Digital Modules
3-90
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Note
The outputs must be protected by a high-speed, fast-acting 3.15 A 250 VAC fuse.
When mounted in a hazardous area in accordance with the National Electric Code,
a tool must be used to remove the fuse and the area must be designated safe
before the fuse is removed/replaced.
Parameterization of the SM 322; DO x 120/230 VAC/2 A ISOL
A description of the general procedure for parameterizing digital modules can be
found in section 3.3.
Detailed information on the digital output module parameters can be found in
Appendix A.3.
Parameters of the SM 322; DO 8 x 120/230 VAC/2 A ISOL
Table 3-22 shows the settable parameters with the default settings for the SM 322;
DO 8 x 120/230 VAC/2 A ISOL.
The default settings apply if you have not performed parameter assignment in
STEP 7.
Table 3-22 Parameters of the SM 322; DO 8 x 120/230 VAC/2 A ISOL
Parameter
Value Range Default
settings
Parameter
type
Scope
Enable
• Diagnostic interrupts Yes/no No Dynamic Module
Behavior on CPU STOP Switch substitute value
(EWS)
Hold last value (LWH)
EWS Dynamic Channel
Switch substitute value
“1”
Yes/no No Dynamic Channel