Analog Modules
4-122
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Special characteristic of channel groups with resistance measurement
If you use the resistance measurement method, there is only one channel per
channel group. The “2nd” channel of each group is used for current injection (I
C
).
The measured value is obtained by accessing the “1st” channel of the group. The
“2nd” channel of the group has the default carry value “7FFF
H
”.
Special characteristic of channel groups for hardware interrupts
You can set hardware interrupts in STEP 7 for the channel groups 0 and 1. Note,
however, that a hardware interrupt is set only for the first channel in the channel
group in each case – in other words, for channel 0 or channel 2
Diagnostics
You will find the diagnostic messages that are grouped under the “group diagnosis”
parameter in Table 4-46, on page 4-72.
4.22.2 Measuring Methods and Measuring Ranges of the SM 331;
AI 8 x 12 bits
Measuring Methods
You can set the following measuring methods for the input channels:
Voltage measurement
Current measurement
Resistance test
Temperature measurement
You perform the setting by means of the measuring range modules on the module
and with the “measuring method” parameter in STEP 7.
Unused Channels
You must short-circuit unused channels and connect them to M
ANA
. In this way,
you obtain an optimum interference immunity for the analog input module. Set the
“measuring method” parameter for unused channels to “disabled”. In this way you
shorten the scan time of the module.
If you do not use the COMP input, you must short-circuit it also.

Table of Contents

Other manuals for Siemens 6ES7 305-1BA80-0AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6ES7 305-1BA80-0AA0 and is the answer not in the manual?

Siemens 6ES7 305-1BA80-0AA0 Specifications

General IconGeneral
BrandSiemens
Model6ES7 305-1BA80-0AA0
CategoryController
LanguageEnglish

Related product manuals