Special Signal modules
5-20
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
5.4.11 Interrupts of the SM 338; POS INPUT
Introduction
In this Section, the interrupt behavior of the SM 338; POS-INPUT is described.
The SM 338 can trigger diagnostic interrupts.
The OBs and SFCs mentioned below can be found in the online Help for STEP 7,
where they are described in greater detail.
Enabling interrupts
The interrupts are not preset – in other words, they are inhibited without
appropriate parameter assignment. Assign parameters to the Interrupt Enable in
STEP 7 (refer to Section 5.4.8).
Diagnostic interrupt
If you have enabled diagnostic interrupts, then incoming active error events (initial
occurrence of the error) and departing error events (message after
troubleshooting) are reported by means of interrupts.
The CPU interrupts execution of the user program and processes the diagnostic
interrupt block (OB 82).
In the user program, you can call SFC 51 or SFC 59 in OB 82 to obtain more
detailed diagnostic information from the module.
The diagnostic information is consistent until such time as OB 82 is exited. When
OB 82 is exited, the diagnostic interrupt is acknowledged on the module.

Table of Contents

Other manuals for Siemens 6ES7 305-1BA80-0AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6ES7 305-1BA80-0AA0 and is the answer not in the manual?

Siemens 6ES7 305-1BA80-0AA0 Specifications

General IconGeneral
BrandSiemens
Model6ES7 305-1BA80-0AA0
CategoryController
LanguageEnglish

Related product manuals