EasyManua.ls Logo

Siemens 6RA70 Series - Page 106

Siemens 6RA70 Series
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Siemens Energy & Automation 9-17
SIMOREG DC Master Base Drive Panel Operating Instructions
Fault Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
20 Current limit is too low
(With speed controller optimization run: Less than 30% or 45% of P100 (I
A,motor
) + the armature current required for zero
speed,
With optimization run for friction moment and moment of inertia compensation: Less than 20% of P100 (I
A, motor
) + the
armature current required for a steady-state speed corresponding to 10% of maximum speed)
21 Field weakening range is too wide (n
act
< +7% n
max
produces |EMF| > 54% setpoint EMF)
(setpoint EMF= K289= P101 – P100
*
P110)
Possible cause:
Maximum speed setting is incorrect
Pulse encoder parameters are incorrect (P140 to P143)
Parameters for tachometer adaptation are incorrect (P741)
Setpoint EMF is not correct (P101, P100, P110)
Caution:
Even a high absolute negative actual speed value can produce an | EMF | of > 54% setpoint EMF
22 With speed controller optimization run:
With an acceleration current equaling 20% or 30% of P100 (I
A, motor
) + armature current required for zero speed or
With optimization run for friction moment and moment of inertia compensation:
With an acceleration current equaling the current required to achieve a steady-state speed of 10% of maximum speed +
20% of P100 (I
A, motor
), the maximum speed cannot be reached within 45s +7%
Possible cause:
Centrifugal mass is too large
Drive is blocked, heavily speed-dependent or excessively high load torque
“Active” load is attempting to maintain a certain speed
Possible remedy:
Increase P100 while the optimization run is in progress in order to raise the applied acceleration current during
optimization (during the speed controller optimization run, a maximum of 45% of I
A, motor
(+ armature current for zero
speed) is applied as the armature current setpoint, I
A,motor
(P100) can thus be increased to 2.2 times the value at
maximum without exceeding 100% I
A, motor
during optimization)
23 With speed controller optimization run:
With an acceleration current equaling 20% or 30% of P100 (I
A, motor
) + armature current required for zero speed or
With optimization run for friction moment and moment of inertia compensation:
With an acceleration current equalling the current required to achieve a steady-state speed of 10% of maximum speed +
20% of P100 (I
A, motor
), the maximum speed or 100% of setpoint EMF cannot be reached within 90s +13%
Possible cause:
Flywheel mass is too large
Drive is blocked, heavily speed-dependent or excessively high load torque
“Active” load is attempting to maintain a certain speed
Possible remedy:
Increase P100 while the optimization run is in progress in order to raise the applied acceleration current during
optimization (during the speed controller optimization run, a maximum of 45% of I
A, motor
(+ armature current for zero
speed) is applied as the armature current setpoint, I
A,motor
(P100) can thus be increased to 2.2 times the value at
maximum without exceeding 100% I
A, motor
during optimization)
24 With speed controller optimization run:
The actual speed does not drop to below +2% of maximum speed or to below the speed threshold n
min
set in P370 within 2
minutes
With optimization run for field weakening:
The actual speed does not drop to below +2% of maximum speed or to below the speed threshold n
min
set in P370 within
10 minutes
With optimization run for friction moment and moment of inertia compensation:
The actual speed does not drop to below +2% of maximum speed or to below the speed threshold n
min
set in P370 within
11 or 2 minutes
Possible cause:
Single-quadrant drive coasts to a standstill too slowly

Table of Contents

Related product manuals