10-52 SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
PNU
Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P492
FDS
(G185)
Analog monitoring of motor temperature: Trip temperature
Operative only when P490.x=1.
0 to 200
[°C]
1°C
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P493
*
FDS
(G185)
Motor temperature analog 1 (temperature sensor at terminals 22 / 23):
Tripping of alarm or fault message
Motor temperature grasped with KTY84
0 Monitoring deactivated
1 Alarm (A029) at temperature > P491
2 Fault message (F029) at temperature > P492
3 Alarm (A029) at temperature > P491 and
fault message (F029) at temperature > P492
Motor temperature grasped with PTC thermistor
0 Monitoring deactivated
1 Alarm message (A029) when operating point of PTC thermistor
is reached
2 Fault message (F029) when operating point of PTC thermistor is
reached
3 Illegal setting
0 to 3
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P494
*
FDS
(G185)
Motor temperature analog 2 (temperature sensor at terminals 204 /
205): Tripping of alarm or fault message
Motor temperature grasped with KTY84
0 Monitoring deactivated
1 Alarm (A029) at temperature > P491
2 Fault message (F029) at temperature > P492
3 Alarm (A029) at temperature > P491 and
fault message (F029) at temperature > P492
Motor temperature grasped with PTC thermistor
0 Monitoring deactivated
1 Alarm message (A029) when operating point of PTC thermistor
is reached
2 Fault message (F029) when operating point of PTC thermistor is
reached
3 Illegal setting
0 to 3
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P495
*
FDS
(G186)
Brush length sensing: Tripping of alarm or fault message
0 No brush length sensing (terminal 211 is not scanned)
1 Binary brush length sensing (terminal 211 is scanned)
Alarm (A025) in response to 0 signal
2 Binary brush length sensing (terminal 211 is scanned)
Fault message (F025) in response to 0 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P496
*
FDS
(G186)
Bearing condition: Tripping of alarm or fault message
0 No bearing condition sensing (terminal 212 is not scanned)
1 Bearing condition sensing (terminal 212 is scanned)
Alarm (A026) in response to 1 signal
2 Bearing condition sensing (terminal 212 is scanned)
Fault message (F026) in response to 1 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P497
*
FDS
(G186)
Air flow: Tripping of alarm or fault message
0 No air flow monitoring (terminal 213 is not scanned)
1 Air flow monitoring (terminal 213 is scanned)
Alarm (A027) in response to 0 signal
2 Air flow monitoring (terminal 213 is scanned)
Fault message (F027) in response to 0 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P498
*
FDS
(G186)
Temperature switch: Tripping of alarm or fault message
0 No temperature switch connected (terminal 214 is not scanned)
1 Temperature switch connected (terminal 214 is scanned)
Alarm (A028) in response to 0 signal
2 Temperature switch connected (terminal 214 is scanned)
Fault message (F028) in response to 0 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline