10-80 SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
PNU
Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P791
*
(G171)
(G173)
Number of process data for G-SST2
When P790 = 0 or 9 is selected:
Parameter is irrelevant
When USS protocol (P790=2) is selected:
Number of PZD elements
0 No process data are expected or sent in the USS protocol
1...16 Number of process data words in USS protocol (same number
applies to transmission and receipt)
The received PZD elements (1 to max. 16) are available at
connectors (K6001 to K6016) and, in some cases, bit-serially at
binectors for "internal wiring" purposes.
The PZD elements to be transmitted (1 to max. 16) are selected
in parameters P794.01 to P794.16.
When peer-to-peer (P790= 5) is selected
: Number of transferred words
0 Illegal setting
1...5 Number of transferred words
6...16 Illegal setting
0 to 16
1
Ind: None
FS=2
Type: O2
P052 = 3
P051 = 40
Offline
P792
*
(G171)
Length of parameter jobs for G-SST2
This parameter is effective only when P790=2 (USS protocol).
0 No PKW data
are expected or sent in the USS protocol.
3, 4 3 or 4 PKW data words
are expected in the USS protocol and 3
or 4 PKW data words are also sent (for transmission of
parameter values).
127 Number of PKWs is determined by the telegram length
0, 3, 4, 127
1
Ind: None
FS=127
Type: O2
P052 = 3
P051 = 40
Offline
P793
*
(G171)
(G173)
Baud rate for G-SST2
1 300 baud
2 600 baud
3 1200 baud
4 2400 baud
5 4800 baud
6 9600 baud
7 19200 baud
8 38400 baud
9 56700 baud
11 93750 baud
13 187500 baud
1 to 13
1
Ind: None
FS=6
Type: O2
P052 = 3
P051 = 40
Offline
P794
*
(G171)
(G173)
Source for transmit data for G-SST2
Selection of connectors to be transferred as transmit data
via basic
converter interface 2
When USS protocol (P790=2) is selected:
i001: Selection for word 1
i002: Selection for word 2
...
i016: Selection for word 16
When peer-to-peer (P790=5) is selected:
i001: Selection for word 1
i002: Selection for word 2
...
i005: Selection for word 5
i006: Not used
...
i016: Not used
Applicable settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 16
FS=
i001: 32
i002: 167
i003: 0
i004: 33
i005-i016: 0
Type: L2
P052 = 3
P051 = 40
Offline