SIEMENS  Energy & Automation   10-35 
SIMOREG DC Master Base Drive Panel  Operating Instructions 
PNU 
 
Description  Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
r218 
(G151)  
(G152) 
Indication of the active integration time of the speed controller 
  [SW 1.7 and later] 
0.010 to 10.000 
[s] 
0.001s 
Ind: None 
Type: O2 
P052 = 3 
r219 
(G151)  
(G152) 
Display of effective P gain of speed controller 
0.01 to 200.00 
0.01 
Ind: None 
Type: O2 
P052 = 3 
 
P221 
 
FDS 
(G152) 
Speed controller: Hysteresis for speed-dependent PI/P controller 
switchover  [SW 1.9 and later] 
See P222 for further details. 
0.00 to 100.00 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FS=2.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P222 
 
FDS 
 
(G152) 
Speed controller: Speed-dependent switchover threshold for PI / P 
controller 
0.00  Automatic switchover from PI to P controller deactivated. 
> 0.00  Depending on the actual speed (K0166), the PI controller 
switches over to a P controller if the speed drops below the 
threshold set in parameter P222. The integrator is not switched 
in again (with value of 0) until the actual speed is > P222 + 
P221. 
This function allows the drive to be stopped without overshoot 
using a zero setpoint with the controllers enabled. 
  This function is active only if the binector selected in P698 is in 
the log. "1" state. 
0.00 to 10.00 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
 
Setting values for speed controller 
P223 
* 
FDS 
(G152) 
Control word for speed controller precontrol 
0  Speed controller precontrol disabled 
1  Speed controller precontrol acts as torque setpoint (is added to 
n controller output) 
0 to 1 
1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P224 
* 
FDS 
(G152) 
Control word for speed controller I component 
0  Set controller I component to 0 (i.e. to achieve a pure P 
controller) 
1  Controller I component is active 
The I component is stopped when a torque or current limit is 
reached 
2  Controller I component is active 
The I component is stopped when a torque limit is reached 
3  Controller I component is active 
The I component is stopped only when ±199.99% is reached 
0 to 3 
1 
Ind: 4 
FS=1 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P225 
 
FDS   
 
(G151) 
Speed controller P gain 
See also setting values for "Speed controller adaptation" function (P550 to 
P559). 
This parameter is set automatically during the speed controller optimization 
run (P051=26). 
0.10 to 200.00 
0.01 
Ind: 4 
FS=3.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P226 
FDS 
(G151) 
Speed controller reset time 
This parameter is set automatically during the speed controller optimization 
run (P051=26). 
0.010 to 10.000 
[s] 
0.001s 
Ind: 4 
FS=0,650 
Type: O2 
P052 = 3 
P051 = 40 
Online 
 
Speed controller droop 
Function:  A parameterizable feedback loop can be connected in parallel to the I and P components of the speed controller (acts on 
summation point of setpoint and actual value). 
P227 
 
FDS   
 
(G151) 
Speed controller droop 
A 10% speed droop setting causes a 10% deviation in the speed from the 
setpoint at a 100% controller output (100% torque or armature current 
setpoint) ("softening" of closed-loop control). 
See also P562, P563, P630 and P684 
0.0 to 10.0 
[%] 
0.1% 
 
Ind: 4 
FS=0.0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
 
P228 
 
FDS 
 
(G152) 
Filter time for speed setpoint 
Filtering of setpoint by means of a PT1 element. 
This parameter is automatically set to the same value as the speed 
controller reset time during the speed controller optimization run (P051=26). 
It may be useful to parameterize lower values when the ramp-function 
generator is in use. 
0 to 10000 
[ms] 
1ms 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online