10-60 SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
PNU
Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P601
*
(G160)
(G161)
(G162)
Source for armature current controller setpoint
i001,i002 Speed limiting controller:
Selection of connectors to be injected as input quantities for
the speed limiting controller. Both values are added.
i003,i004 Current limitation:
Selection of connectors to be injected as armature current
controller setpoint (before current limitation). Both values are
added.
i005,i006 Current control: [SW 1.8 and later]
Selection of which connectors are connected as the armature
current controller setpoint (before current controller). The
two values are added. The magnitude is formed from the
value selected with index 6.
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 6
FS=
i001: 141
i002: 0
i003: 134
i004: 0
i005: 125
i006: 0
Type: L2
P052 = 3
P051 = 40
Offline
P602
*
(G162)
Source for armature current controller actual value
Selection of connector to be injected as armature current controller
actual value
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=117
Type: L2
P052 = 3
P051 = 40
Offline
P603
*
(G161)
Source for variable current limit in torque direction I
i001..i004 Selection of connector to be injected as variable
current limit
in torque direction I
Normalization: +100% corresponds to P100*P171
i005 Selection of connector to be injected as current limit in torque
direction I with Fast Stop or Shutdown
Normalization: +100% corresponds to P100*P171
i006 Selection of connector to be injected as variable
current limit
in torque direction I
Normalization: +100% corresponds to r072.002
[can be set in SW 1.9 and later]
i007 Selection of connector to be injected as current limit in torque
direction I with Emergency Stop or Shutdown
Normalization: +100% corresponds to r072.002
[can be set in SW 1.9 and later]
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 7
FS=
i001: 1
i002: 1
i003: 1
i004: 1
i005: 1
i006: 2
i007: 2
Type: L2
P052 = 3
P051 = 40
Offline