10-34 SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
PNU
Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P184
FDS
(G160)
Threshold speed for torque limits
If "Torque limit switchover" is selected (state of binector selected in P694
=1) and the speed (K0166) is higher than the threshold speed set in
parameter P184, then torque limit 2 (P182, P183) is activated in place of
torque limit 1 (P180, P181).
0.00 to 120.00
[%]
0.01%
of maximum speed
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P190
FDS
(G162)
Filter time for setpoint for armature current precontrol
[SW 1.9 and later]
Filtering of the armature current setpoint at the input of the precontrol for the
armature current controller.
The purpose of this filter is to decouple the armature current precontrol from
the armature current controller.
0 to 10000
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
on-line
P191
FDS
(G162)
Filter time for setpoint for armature current controller
[SW 1.9 and later]
Filtering of the armature current setpoint at the input of the armature current
controller.
The purpose of this filter is to decouple the armature current precontrol from
the armature current controller.
0 to 10000
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
on-line
10.10 Auto-reversing stage, armature gating unit
P192
*
FDS
(G163)
Control word for the Alpha W limit (armature) [as of SW 2.1]
0 Continuous current:
Inverter stability limit for the delay angle of the armature
converter (Alpha W) = value according to parameter P151
Intermittent current:
Alpha W = 165°
1 Inverter stability limit for the delay angle of the armature
converter (Alpha W) = value according to parameter P151
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
10.11 Speed controller
further parameters for the speed controller P550 - P567
Setting values for speed controller - actual value/setpoint processing
P200
FDS
(G152)
Filter time for actual speed controller value
Filtering of the actual speed value by means of a PT1 element.
This filter setting is taken into account by the speed controller optimization
run (P051=26).
0 to 10000
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P201
FDS
(G152)
Band-stop 1: Resonant frequency
1 to 140
[Hz]
1Hz
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
Online
P202
FDS
(G152)
Band-stop 1: Quality
0 Quality = 0.5
1 Quality = 1
2 Quality = 2
3 Quality = 3
0 to 3
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P203
FDS
(G152)
Band-stop 2: Resonant frequency
1 to 140
[Hz]
1Hz
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
Online
P204
FDS
(G152)
Band-stop 2: Quality
0 Quality = 0.5
1 Quality = 1
2 Quality = 2
3 Quality = 3
0 to 3
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P205
FDS
(G152)
D element: Derivative-action time
0 to 1000
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P206
FDS
(G152)
D element: Filter time
0 to 100
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
r217
(G151)
Indication of the active droop of the speed controller [SW 1.7 and later]
0.0 to 10.0
[%]
0.1%
Ind: None
Type: O2
P052 = 3