EasyManua.ls Logo

Siemens 6RA70 Series - Access Authorization Levels

Siemens 6RA70 Series
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SIEMENS Energy & Automation 10-11
SIMOREG DC Master Base Drive Panel Operating Instructions
PNU
Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P046
*
(G121)
Binector display:
i001: Selection of binector displayed in r045.01
i002: Selection of binector displayed in r045.02
i003: Selection of binector displayed in r045.03
i004: Selection of binector displayed in r045.04
All binector numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Online
r047 Display of fault diagnostic memory
Provides more detailed information about the cause of a fault after activation
of a fault message (see Section 10).
i001 Word 1 (fault value)
i002 Word 2
...
i016 Word 16 (fault number)
0 to 65535
1
Ind: 16
Type: O2
P052 = 3
r048
(G189)
Hours run
Display of time (hours) in which drive has been operating in states I, II or - -.
All times of approx. 0.1 s are included in the count.
0 to 65535
[hours]
1 hour
Ind: None
Type: O2
P052 = 3
r049
(G189)
Fault time
Display of time at which the current fault, and the last 7 acknowledged
faults, were activated.
i001: Current fault hours
i002: 1
st
acknowledged fault hours
i003: 2
nd
acknowledged fault hours
i004: 3
rd
acknowledged fault hours
i005: 4
th
acknowledged fault hours
i006: 5
th
acknowledged fault hours
i007: 6
th
acknowledged fault hours
i008: 7
th
acknowledged fault hours
0 to 65535
[hours]
1 hour
Ind: 8
Type: O2
P052 = 3
P050
*
Language
Language of plaintext display on optional OP1S operator panel and in
DriveMonitor PC service routine
0: German
1: English
2: Spanish
3: French
4: Italian
0 to 4
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 0
Online
10.3 Access authorization levels
P051
*
Key parameters
0 No access authorization
6 Do not set (for use by DriveMonitor)
7 Do not set (for use by DriveMonitor)
9 Do not set (for use by DriveMonitor)
21 Restore factory settings
All parameters are reset to their defaults (factory settings).
Parameter P051 is then automatically reset to factory setting
"40".
22 Execute internal offset compensation (see Section 7.4)
25 Optimization run for precontrol and current controller (armature
and field) (see Section 7.5)
26 Optimization run for speed controller (see Section 7.5)
27 Optimization run for field weakening (see Section 7.5)
28 Optimization run for compensation of friction and moment of
inertia (see Section 7.5)
29 Optimization run for the speed controller with an oscillating
mechanical system (see Section 7.5)
40 Access authorization to parameter values for authorized service
personnel
see column on left Ind: None
FS=40
Type: O2
P052 = 3
P051 0
Online
P052
*
Selection of display parameters
0 0 Display only parameters that are not set to original factory
settings
1 Display only parameters for simple applications
3 Display all parameters used
0, 1, 3 Ind: None
FS=3
Type: O2
P052 = 3
P051 0
Online

Table of Contents

Related product manuals