Commissioning security module (firewall) FN2009
-
A1
Entering network settings
18
102 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
2. Select the 'Routing Mode' tab.
a The following entry mask is displayed:
3. Check the 'Routing active' checkbox.
4. Enter the following 'internal module IP address': 192.168.201.2.
5. Confirm input with 'OK'.
a 'Internal sub-net mask' is automatically created.
a 'Routing Mode' is active.
Entering router network data, 'Router'
The following settings apply for the planned network access to GAP with activated
DHCP server.
1. Open the 'Module Properties' window again.
a The 'Network' tab is displayed.
2. Click on 'Add Router'.
a The 'Sub-net Mask' '255.255.255.0' is already entered.
3. Correct the 'Sub-net Mask' from '255.255.255.0' to '255.255.0.0'.
4. Enter the following network data:
'Router IP': 192.168.201.1
'Network ID': 192.168.0.0
5. Confirm input with 'OK'.
a The router network data is entered.