Commissioning security module (firewall) FN2009
18
103 |
Building Technologies
Loading the network settings to FN2009-A1
w MAC address is entered.
w IP addresses are entered.
1. Highlight the FN2009-A1 module in the project.
2. Select the 'Transfer > 'To Module' menu.
a The network settings are loaded to FN2009-A1.
a Network settings are entered.