Updating the firmware
Station: Updating the FW
of the main CPU and additional CPUs
22
120 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
22.2.4.2 PMI & mainboard FCM2027
w You are familiar with the information in chapter 'Preparation and security
[ 113]'.
1. Select 'Update' > 'FW update main and additional CPUs' from the menu bar.
2. If the 'Password check' window opens, enter the password '12345678' and click
on 'OK'.
3. NOTICE! Data loss. Save the configuration data before updating the firmware.
Saving the configuration data also backs up specific system data which is
only available on the 'Station'. This includes modified customer texts, time
stamps of recent alarms, or persistent commands.
a The 'FW update main and additional CPUs' window opens.
4. Select the desired firmware version.
5. The firmware update can be started in two ways:
Start the firmware update in Cerberus-Engineering-Tool.
or
Start the firmware update at the 'Station'. The procedure is described in
the following section.
Initializing the '
Station
' instead of installing the
BDV saves time. During
initialization, the BDV and the configuration data are loaded to the 'Station'.
You will find information on troubleshooting for the firmware update in chapter
'Error during firmware update [ 124]'.