Updating the firmware
Station: Updating the FW of the main CPU and additional CPUs
22
119 |
178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
4. Click on 'OK' in the 'Information' window.
a The following window is opened:
5. Select 'Run in background' in order to run the firmware update in the
background while continuing to work in Cerberus-Engineering-Tool.
a The active firmware update is indicated by the symbol on the right-
hand side of the status bar.
a Pop-up windows in the bottom right-hand corner of the software will notify
you when the firmware download and the firmware update are complete.
6. Follow the procedures on the display of the 'Station' and wait until the
following lines appear:
'Switch-off S38-2 now'
'The panel will reboot automatically'
7. On the 'Station', set the 'S38-2' switch to 'OFF'.
a The 'Station' is restarted many times. This procedure takes up to ten
minutes.
a After the restart, the 'Station' display shows the available BDVs. It is not
necessary to install a BDV at this point.