Changing and expanding the FDnet/C
-
NET d
etector line
Removing or replacing non
-
stationary devices
12
52 | 178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
12.4.2.1 Temporarily removing an individual non-stationary device
Instances may arise when a C-NET device has to be temporarily removed from the
base. Afterwards the same device must be re-inserted at exactly the same place in
the C-NET.
Mark the allocation of the devices to the respective base to avoid additional work
steps.
You will find additional information about the individual
steps on the specified
pages.
1. Switch the C-NET detector line off. Link [ 79]
2. Remove the C-NET device from its base.
3. Perform the tasks.
4. Re-insert the C-NET device in the corresponding position.
5. Switch the C-NET detector line on. Link [ 79]
If detectors have been swapped over or are missing, the following messages are
shown on the display of the Person Machine Interface:
'Zone', 'Serial no. ("ID-Nr.")', 'Dev.location fault'
See also
2 Correcting swapped devices [ 158]
12.4.2.2 Replacing non-stationary devices of the same type
You will find additional information about the individual steps on the specified
pages.
1. Switch the C-NET detector line off. Link [ 79]
2. Replace the C-NET device with a device of the same type. Several devices can
be replaced.
3. Rectify localization errors. Link [ 86]
4. Connect the PC to the 'Station'. Link [ 27]
5. Load the configuration from the 'Station' to the PC. Link [ 32]
6. Disconnect the PC from the 'Station'. Link [ 27]