Changing and expanding the FDnet/C
-
NET detector line
Removing or replacing non
-
stationary devices
12
53 |
178
Building Technologies
A6V10210416_j_en_
--
Fire Safety
2018
-
-
29
12.4.2.3 Replacing a non-stationary device of a different type
You will find additional information about the individual steps on the specified
pages.
1. Switch the C-NET detector line off. Link [ 79]
2. Remove the C-NET device from its base.
a The 'Station' detects that the device is missing and reports a 'Fault'.
3. Delete the C-NET device individually on the Person Machine Interface on the
control panel. Link [ 83]
4. Insert the new C-NET device in the base.
5. Read-in the C-NET devices. Link [ 82]
6. Connect the PC to the 'Station'. Link [ 27]
7. Load the configuration from the 'Station' to the PC. Link [ 32]
8. Replace the C-NET device in the 'Zone'. Link [ 53]
9. Load the configuration from the PC to the 'Station'. Link [ 30]
10. Disconnect the PC from the 'Station'. Link [ 27]
Replacing a device in the 'Zone'
1. Select the 'Zone' in which you have replaced a device in Cerberus-
Engineering-Tool. The 'Find' or 'Find and replace' functions can be used to do
this.
2. Replace the C-NET device.
You will find more information in document A6V10210424. See chapter 'Applicable
documents'.