Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
176 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Byte.Bit
Designation (PRM group)
Type
Range
Unit
Default
Note
Information
8.7 Voltage measuring module
(UM)
Bit 0, 1 BU2(+)
9.0
Reserved
10.0 Control function (CF) 0x00
0x10
0x11
0x12
0x20
0x21
0x30
0x31
0x40
0x41
0x50
0x60
0x61
0x62
0x63
0x64
0x70
0x71
0x00 = Overload
0x10 = Direct starter
0x11 = Reversing starter
0x12 = 3VL molded case
circuit breaker (MCCB)
0x20 = Star-delta starter
0x21 = Star-delta
reversing starter
0x30 = Dahlander starter
0x31 = Dahlander
reversing starter
0x40 = Pole-changing
starter
0x41 = Pole-changing
reversing starter
0x50 = Solenoid valve
0x60 = Positioner 1
0x61 = Positioner 2
0x62 = Positioner 3
0x63 = Positioner 4
0x64 = Positioner 5
0x70 = Soft starter
0x71 = Soft starter with
reversing contactor
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU1 BU2(+)
BU0 BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU2(+)
BU0 BU2(+)
BU2(+)
11.0
Reserved
Bit[8]
12.0
Bit parameters (16)
12.0 No configuration fault due
to OP
Bit 0, 1 0 BU0 BU1 BU2(+)
12.1 Startup parameter block
active
Bit 0, 1 1 BU0 BU1 BU2(+)
12.2
Test / Reset keys disabled
Bit
0, 1
0
BU0 BU1 BU2(+)
12.3 Bus and PLC/PCS - Reset Bit 0, 1 0 0 = Manual
1 = Auto
BU0 BU1 BU2(+)
12.4
Reserved
Bit
0
12.5
Reserved
Bit
0
12.6
Reserved
Bit
0
12.7
Reserved
Bit
0
13.0 Diagnostics for process
events
Bit 0, 1 0 BU0 BU1 BU2(+)
13.1 Diagnostics for process
warnings
Bit 0, 1 1 BU0 BU1 BU2(+)
13.2 Diagnostics for process
faults
Bit 0, 1 1 BU0 BU1 BU2(+)