Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
177
Byte.Bit
Designation (PRM group)
Type
Range
Unit
Default
Note
Information
13.3 Diagnostics for device
faults
Bit 0, 1 1 BU0 BU1, BU2(+)
13.4
Reserved
Bit
0
13.5
Reserved
Bit
0
13.6 Bus monitoring Bit 0, 1 1 BU0 BU1 BU2(+)
13.7
PLC/PCS monitoring
Bit
0, 1
1
BU0 BU1 BU2(+)
14.0 Overload protection - Load
type
Bit 0, 1 0 0 = 3-phase
1 = 1-phase
IM UM(+)
14.1 Overload protection - Reset Bit 0, 1 0 0 = Manual
1 = Auto
IM UM(+)
14.2
Reserved
Bit
0
14.3 Save change-over
command
Bit 0, 1 0 BU0 BU1 BU2(+)
14.4 Non-maintained command
mode
Bit 0, 1 0 BU0 BU1 BU2(+)
14.5 Cold start level (TPF) Bit 0, 1 0 0 = NO contact
1 = NC contact
BU0 BU1 BU2(+)
14.6 Type of consumer load Bit 0, 1 0 0 = Motor
1 = ohmic load
BU0 BU1 BU2(+)
14.7
Reserved
Bit
0
15.0
External fault 1 - Type
Bit
0, 1
0
0 = NO contact
1 = NC contact
BU0 BU1 BU2(+)
15.1
External fault 2 - Type
Bit
0, 1
0
BU0 BU1 BU2(+)
15.2
External fault 3 - Type
Bit
0, 1
0
BU0 BU1 BU2(+)
15.3 External fault 4 - Type Bit 0, 1 0 BU0 BU1 BU2(+)
15.4 External fault 1 - active
status
Bit 0, 1 0 0 = Always
1 = Only motor ON
BU0 BU1 BU2(+)
15.5
External fault 2 - Activity
Bit
0, 1
0
BU0 BU1 BU2(+)
15.6
External fault 3 - Activity
Bit
0, 1
0
BU0 BU1 BU2(+)
15.7
External fault 4 - Activity
Bit
0, 1
0
BU0 BU1 BU2(+)
16.0
Bit[2] - Parameters (20)
16.0 Thermistor - Overload
response
Bit[2] 1, 2, 3 3 0 = disabled
1 = signaling
2 = warn
3 = tripping
Th
16.2 Thermistor - Response to
sensor fault
Bit[2] 0, 1, 2, 3 2 Th
16.4 Internal ground fault -
Response
Bit[2] 0, 1, 2, 3 0 BU0 BU1 BU2(+)
16.6 Motor protection - Overload
response
Bit[2] 0, 1, 2, 3 3 IM
17.0 Motor protection - Overload
response
Bit[2] 0, 1, 2 2 IM
17.2 Unbalance protection -
Response
Bit[2] 0, 1, 2, 3 2 IM
17.4
Trip response I>
Bit[2]
0, 1, 3
0
BU0 BU1 BU2(+)
17.6
Warning response I>
Bit[2]
0, 1, 2
0
BU0 BU1 BU2(+)
18.0
Trip response I<
Bit[2]
0, 1, 3
0
BU0 BU1 BU2(+)