Communication
2.2 PROFINET communication
SIMOCODE pro - Communication
88 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Connection monitoring
The OPC UA connection is monitored over time. The monitoring time is set by the OPC UA
client and is in the range of 10 s to 100 s. If the OPC UA connection is terminated, the
OPC UA control variables set by this OPC client will be deleted in SIMOCODE pro only after
this time has expired. In SIMOCODE pro, no fault is triggered.
If failure of the OPC UA connection of SIMOCODE pro is to be monitored, this can be done
as follows:
WARNING
The drive cannot be controlled.
Can result in death, serious injury, or property damage.
If the connection is interrupted, the drive cannot be controlled while the OPC-UA
connection monitoring time is active.
Take suitable safety measures to avoid personal injury or property damage.
Example:
Makes sure that Bit 0.7 is set statically at the client end. If the connection is interrupted, this
will activate the "PLC/PCS" fault in "remote" mode (mode selector S1=1, S2=1).
Figure 2-26 Example of connection monitoring

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals