Configuration
5-8 7SJ62 Manual
C53000-G1140-C121-1
For double commands, the first output relay is selected using DIGSI
®
4. The other out-
put relays will automatically be selected by DIGSI
®
4. In the sequence of output relays,
each TRIP command is placed before the associated CLOSE command. For
commands with processing of feedback indications, DIGSI
®
4 reserves a line in the
configuration matrix for the switching device feedback indications. The 52b contact
must be placed before the 52a contact.
For Figures 5-4 through 5-9, the following abbreviations apply:
C+ Relay Contact for Closing
C– Relay Contact Tripping
CC Relay Contact is Common
CCC Relay Contact is Common to a Bus
V+, V– Control Voltage
Figure 5-4 Single Command with Single Output
Figure 5-5 Double Command with Single Contacts
Double Command with Single
Outputs and Common Bus Output
Minimum 3
contacts
without feedback
with feedback
C_D2
CF_D2
Double Command with Double
Outputs
With 4 contacts without feedback
with feedback
&B'
&)B'
Double Command with Double
(Close) and Single (Trip) Outputs
With 3 contacts without feedback
with feedback
&B'
&)B'
Table 5-1 Most Important Command Types
CLOSING
C+
t
Switching
Device
C+
V+
V–
Relay Configuration:
COMMAND
C+
X
BO 1
CLOSE
COIL
C+
C–
t
C+
C–
V+
V–
Relay Configuration:
Command
CLOSE
Command
TRIP
C+
X
BO 1
C
X
2
CLOSE TRIP
Switching Device
COIL COIL
www . ElectricalPartManuals . com