EasyManua.ls Logo

Siemens TIM 4R-IE DNP3 - Page 179

Siemens TIM 4R-IE DNP3
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
System Manual, 06/2014, C79000-G8976-C253-03
179
project. The parameter area for the destination subscriber-specific parameters is opened and
the parameters are set for every configured destination subscriber.
The following destination subscriber-specific parameters are available:
Parameters of the DNP3 master station
Name:
DNP3 implementation level
Range of
values:
1 ... 5
Default:
3
Explanation:
With the SINAUT configuration software, you can specify the DNP3
implementation level for each configured DNP3 master station (subscriber
type: other station). Specify the highest conformity level supported by the
DN
P3 master station.
Values can be assigned in the range from 1 to 5. Based on this information,
the TIM firmware selects the suitable standard variations of the process
data for this master station.
Level 5 that is not specified in the standard corresponds
to implementation
level 4 and additionally includes the support of the following objects / data
types (object group/variation):
Frozen counter with time of day in 16-bit format (21/6)
Counter event with time of day in 16-bit format (22/6)
Analog input, floating point, 32-bit format (30/5)
Analog input event, floating point with time, 32-bit format (32/7)
Analog output status, floating point, 32-bit format (40/3)
Analog output, floating point, 32-bit format (41/3)
Name:
Time stamp
Default:
Function activated
Explanation:
When using DNP3, the parameter is always activated. This cannot be
deactivated.
The parameter assignment is only practical if the DNP3 master station was
selected as the destination subscriber.
Data read by the local CPU is given a time
stamp before it is sent to the
destination subscriber.

Table of Contents

Related product manuals