The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
216 System Manual, 12/2015, C79000-G8976-C253-04
Mask
Individual bits of the byte to be sent can be blocked using the disable mask for command
acquisition:
Name:
Disable mask
Range of va
l-
ues:
Mask in hexadecimal format
Default:
00 (hex)
Explanation:
Masked bits in the byte of the "Command send" channel are ignored when
changes are checked. This means that changes to the masked bits for this
channel do not trigger message transmission. A masked bit always has the
value 0 in the message.
The corresponding bits are masked in hexadecimal format.
The bits are masked as shown in the following example in which the hexadecimal value A3
is entered in the input field of the parameter assignment dialog. The bits with the value 1 are
masked; in other words bits no. 0, 1, 5 and 7 are ignored in command acquisition.
Byte assignment
Bit no.
7
6
5
4
3
2
1
0
Masked
1
0
1
0
0
0
1
1
Hexadecimal mask
A
3
Cmd01B_R
Channel "CommandOutputByte"
Channel type: Command receive
The object occupies 1 index.
Cmd01B_R it is intended for the station and is pointless for a master station.
Cmd01B_R allows receipt of a binary command. Only the least significant bit 0 of the
transferred byte can be used. The other bits are set to zero.
Only ON commands (bit status 1) are accepted.
As the data destination of the command, a byte variable of the S7 CPU is specified.
Control Code "LATCH_OFF"
Automatic resetting of the bit: In the station, the object resets a bit set by the master station
back to zero immediately if the command output time (see below) is set to zero.
LATCH_OFF is not used if the command output time is set higher than zero.
Name:
Command output time
Range of va
l-
ues:
0 ... 50 [s x 0.1] (tenths of seconds; 5 = 0.5 seconds)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens TIM 4R-IE DNP3 and is the answer not in the manual?

Siemens TIM 4R-IE DNP3 Specifications

General IconGeneral
BrandSiemens
ModelTIM 4R-IE DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals