The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
System Manual, 06/2014, C79000-G8976-C253-03
231
Table 6- 8 Value range of the MODBUS write status
Code
Meaning
0x7002
Job executed without errors
0x8000
Job executed with error
0x8001 Illegal Function
After this error occurs, the S7 address of this write job is no longer read until the
next restart on the TIM.
0x8002
Illegal Data Address
0x8003
Illegal Data Value
0x8004
Slave Device Failure
0x8005
Message transferred but slave device busy with a different process (Acknowledge)
0x8006
Slave Device Busy with other process
0x8008
Memory Parity Error
0x800C
Wrong CRC check value in the response message of the slave
0x800D
Wrong net data in the response message of the slave
0x800E Wrong slave address in the response message of the slave
After this error occurs, the S7 address of this write job is no longer read until the
next restart on the TIM.
0x800F Wrong function code in the response message of the slave
0x8010
No response (send timeout exceeded)
6.6.14.3
The "ModbusRead" object
The "ModbusRead" object
To map the data to be read between the MODBUS slaves and S7 CPU, the "ModbusRead"
object is available. A separate "ModbusRead" object is configured for each MODBUS slave.
MODBUS input
The register address on the MODBUS slave from which the data is read is specified here.
Name:
MODBUS input
Register
ad
dress:
Specifies the register address.
You will find the permitted address ranges in the documentation of your
MODBUS slave.
Range of
values:
0...65535