9-17
4007ES Panel Programmer Manual (579-1167)
Custom Control, Continued
Common Ground
Fault LED Control
Select and utilize the LED Yellow point type for custom control ground fault LED trouble
indications:
Program the Color User Interface, Point Editing Tab as follows:
Add the following custom control equation to the 4007ES IDNAC Addressable Panel:
[INPUTS]
STATUS ON
1-0-9 | CARDSTAT | CSP | POSTIVE EARTH
OR STATUS ON
1-0-10 | CARDSTAT | CSP | NEGATIVE EARTH
OR STATUS ON
1-0-27 | CARDSTAT | CSP | POSITIVE EARTH ON RUI
OR STATUS ON
1-0-28 | CARDSTAT | CSP | NEGATIVE EARTH ON RUI
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY | COMMON GROUND FAULT LED
[END OUTPUTS]
Add the following custom control equation to the 4007ES Hybrid Panel:
[INPUTS]
STATUS ON
1-0-3 | CARDSTAT | CSP | POSITIVE EARTH GROUND
OR STATUS ON
1-0-4 | CARDSTAT | CSP | NEGATIVE EARTH GROUND
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY | COMMON GROUND FAULT LED
[END OUTPUTS]
HW Ref. Switch Mode Ref. Address Ref. Label HW Ref. LED Mode
3-1-1 SMPL 3-2-1 ON P535 Ground Fault
3-1-2 SMPL 3-2-2 SMPL
3-1-3 SMPL 3-2-3 SMPL