A-11
4007ES Panel Programmer Manual (579-1167)
Releasing Specific Controls and Indications, Continued
Abort Switch
Trouble during
Normal
Supervisory
Conditions
2. Configure three unused digital pseudo points to be used as two new troubles and a
supervisory point. Label them as follows (change HAZNAME to the appropriate label for
your hazard area):
3. In the Suppression Release Wizard that you are working on, right click the title (next to
the wizard graphic) and select Properties to open the Hazard Area.
4. Select the points tab and write down the lists assigned to Abort Switches and Automatic
Release Points.
5. Enable Manual Editing of the suppression release wizard equations.
Right click the wizard for that hazard and select Enable Manual Edit. Click Yes in the
confirmation box.
Continued on next page
IMPORTANT: When you enable manual edit the Suppression Release Wizard cannot be
used to modify this hazard area.