5-7
Setting Example:
(1) If Tn103 is set to 300, it means Analog Input Voltage 10V corresponds to 300% rated Torque
Command; if Input Voltage is 5V at this time, then it corresponds to 150% rated Torque
Command.
(2) If Tn103 is set to 200, it means Analog Input Voltage 10V corresponds to200% rated Torque
Command; if Input Voltage is 5V at this time, then it corresponds to 100% rated Torque
Command.
105
-5-10
Torque
Command (%)
Input
Voltage (V)
Slope is set by
Tn103
400
200
-400
-200
600
-600
Even if the Torque Command is 0V, the Motor may rotate slowly, mainly due to a slight offset of
External Analog Voltage, in this case, the user can manually adjust the Tn104 to correct the offset or
use dn-07 to automatically adjust the offset. Please refer to "3-3 Diagnostic Function Description".
Attention
Please confirm the status is Servo off before adjustment; Input 0V voltage command from the
supervisory controller or external loop to analog command connect TIC (CN1-27).