5-82
 
5-4-8 Torque Limit of Position Mode
 
In Position Control, Motor Torque Limit is achieved by switching the following two methods 
using Digital Input Contact TLMT: 
(1) Internal Torque Limit: Use internally to set Cn010, Cn056 (CCW Direction Torque 
Command Limit Value) and Cn011, Cn057 (CW Direction Torque Command Limit Value). 
 External Pulse Command Mode does not have two-stage Torque Limit 
(2) External Analog Command Torque Limit: Use Analog Voltage Command Signal input to 
TIC (CN1-27) to limit the CCW Direction Torque and CW Direction Torque. 
 
Please refer to the Table below:   
Digital input 
contact TLMT 
CCW Direction Torque Command 
Limit Source 
CW Direction Torque Command 
Limit Source 
OFF (Switch 
functions) 
Under external pulse command mode: 
Cn010 
Under internal position command mode: 
Cn010, Cn056 
Under external pulse command mode: 
Cn011 
Under internal position command mode: 
Cn011, Cn057 
ON (Switch 
does not 
function) 
External analog torque limit 
TIC(CN1-27) 
 JSDG2S-E(L) does not have this 
function 
External analog torque limit 
TIC(CN1-27) 
 JSDG2S-E(L) does not have this 
function 
Note) Please refer to “5-6-1 Digital Input / Output Contact Function Planning” to set the Driver 
Effective Logic. 
 
 
Attention 
When using External Analog Torque Command Limit, if this Analog Torque Command Limit 
is greater than the Internal Torque Command Limit, then the Internal Torque Command 
Limit is ultimately used. 
 
(1) Internal Torque Limit: The following is the Internal Torque Limit setting description: 
 
Cn010/Cn056 CCW Direction Torque Command Limit Value Stage 1 / Stage 2 
Initial Value  Unit  Setting Range  Effective  RS-485 Address 
200 ~ 300 
Note) 
%  0 ~ 300  Effective after Set 
Each Parameter is 
different 
Note) Default and setting range of parameter Cn010/Cn056/Cn011/Cn057 vary by driver model. Refer 
to “7-3-1 System parameters (Cn0□□)” for details.