5-186
 
Cn087 EMC stop speed linear deceleration constant 
Initial Value  Unit  Setting Range  Effective  RS-485 Address 
1  ms  0 ~ 50000 
Takes effect after 
confirmation 
005AH 
Setting description: Set Cn097.1=1 to enable the EMC stop speed command deceleration function. 
The definition of the speed command linear deceleration constant is the time for the rated rotation 
speed to decelerate linearly to zero. 
 
 
Decelerationtime 
Ratedrotationspeed
Actionrotationspeed
087
Speed command
Time (ms)
Cn087
Rated rotation speed
Action rotation speed
 
§ Emergency stop (EMC) reset method 
Cn002.3 EMC reset mode selection 
Initial Value  Unit  Setting Range  Effective  RS-485 Address 
0  --  0 ~ 1  Power reset  0002H 
Setting description: 
 
Setting 
Description 
0 
After the emergency stop status is released, the digital input 
contact ALRS can be used to release the AL.009 display only 
under Servo Off status. 
Note) It cannot be cleared under Servo On status. 
1 
After emergency stop status is released, whether under Servo On 
or Servo Off status, the AL.009 display can be reset and released 
automatically. 
!Note: Under Servo On status, before the alarm is cleared and 
returned to normal operation, you must confirm whether the 
controller is still sending commands to the driver in order to 
prevent causing the motor to be out of control!