7-41
Setting Description:
Cn039 Communication Timeout Setting
8-1
Initial Value Unit Setting Range Effective Cn029 Reset
0 sec 0 ~ 20
--
RS-485 CANopen EtherCAT Pi Pe Pt S T
002AH 2027H 2027H O O O O O
Setting Description: If the setting value is greater than 0, the Communication Timeout Function is turned on immediately
and must conduct communication within the set time, otherwise, a communication error will appear.
If the setting value is 0, then indicates this function is turned off.
Cn040 Communication response delay time
8-1
Initial Value Unit Setting Range Effective Cn029 Reset
0 0.5ms 0 ~ 255
--
RS-485 CANopen EtherCAT Pi Pe Pt S T
002BH 2028H 2028H O O O O O
Setting Description: Delay the communication time of Driver responding to Supervisory Control Unit.
Cn041.0 Absolute type encoder multi-revolution clearing function
5-6-10
Initial Value Unit Setting Range Effective Cn029 Reset
0 -- 0 ~ 2 -- --
RS-485 CANopen EtherCAT Pi Pe Pt S T
002CH 2029H 2029H O O O O O
Setting Description:
Setting Description
0 Not Functioning
1 Clear the Encoder Internal Status
2 Clear the Encoder Internal Status and Number of Revolutions
Setting Description Setting Description
0 7 , N , 2 ( Modbus , ASCII ) 5 8 , O , 1 ( Modbus , ASCII )
1 7 , E , 1 ( Modbus , ASCII ) 6 8 , N , 2 ( Modbus , RTU )
2 7 , O , 1 ( Modbus , ASCII ) 7 8 , E , 1 ( Modbus , RTU )
3 8 , N , 2 ( Modbus , ASCII ) 8 8 , O , 1 ( Modbus , RTU )
4 8 , E , 1 ( Modbus , ASCII ) -