7-65
Sn205.1 S-type speed command unit
5-3-4
Initial Value Unit Setting Range Effective Cn029 Reset
0 -- 0 ~ 1 -- --
RS-485 CANopen EtherCAT Pi Pe Pt S T
0205H 2205H 2205H -- -- -- O --
Setting Description:
Setting Description
0
Modify Sn208~210
Unit: 1ms
1
Modify Sn208~210
Unit: 10ms
Sn206 Speed Command One Time Smoothing Acceleration / Deceleration Time
Constant
5-3-4
Initial Value Unit Setting Range Effective Cn029 Reset
1 ms
1-10000 -- --
RS-485 CANopen EtherCAT Pi Pe Pt S T
0206H 2206H 2206H -- -- -- O --
Setting Description: Set Sn205=1 to activate Speed Command One time Smoothing Acceleration / Deceleration Function.
The definition of Speed Command One Time Smoothing Acceleration / Deceleration Time Constant
is the time for the Speed one time delayed rise from Zero Speed to 63.2% of the Speed Command, the
schematic diagram is as follows: