Performance  Check  Procedure
3.  CH  3  and  CH  4  VOLTS/DIV Trace  Shift
a.  Set VERTICAL  MODE to  CH  3  (CH  2  off).
b.  Position trace  to the  center horizontal  graticule  line.
c.  Switch  CH  3  VOLTS/DIV between  0.1  V  and  0.5  V.
d.  CHECK—trace  shift  does  not  exceed  one  division.
e.  Set VERTICAL  MODE to  CH 4  (CH  3  off).
f.  Position  trace  to the  center horizontal  graticule line.
g.  Switch  CH  4 VOLTS/DIV between 0.1  V  and  0.5  V.
h.  CHECK—trace  shift  does  not  exceed  one division.
4.  CH  1  and  CH  2  VAR VOLTS/DIV Trace  Shift
a.  Set:
VERTICAL  MODE  CH  1  (CH 4 off)
CH  1  VOLTS/DIV  2  mV
b.  Position trace to  center  graticule  line.
c.  Set  CH  1  VAR VOLTS/DIV fully  CCW  (counterclockwise).
d.  CHECK—trace shift  does  not  exceed  one  division.
e.  Set:
CH  1  VAR VOLTS/DIV  Detent  (calibrated)
VERTICAL  MODE  CH  2  (CH  1  off)
CH  2  VOLTS/DIV  2  mV
f.  Position trace to center graticule  line.
g.  Set  CH  2  VAR VOLTS/DIV fully CCW.
h.  CHECK—trace  shift  does not  exceed  one division.
i.  Set CH  2 VAR  VOLTS/DIV to  detent  (calibrated)  position.
7-12
2245A  Operators